Eaton’s Cooper Power series 200 A, 25 kV Class Loadbreak Portable Feedthru provides two internally bused 15.2/26.3 kV loadbreak interfaces meeting all requirements of IEEE Std 386™ standard – Separable Insulated Connector Systems. It is used in pad-mounted equipment, underground vaults, and other apparatus to bypass transformers, to test and ground circuits, and to provide open point deadfront lightning arrester protection when used with the Cooper Power Systems M.O.V.E. Arrester. Sectionalizing of cable runs, to find and isolate cable faults, is made easy when the portable feedthru is used with 25 kV Class (15.2/26.3 kV) loadbreak elbows and other accessories meeting the requirements of IEEE Standard 386™. When mated with comparably rated products, the portable feedthru provides a fully shielded, submersible, separable connection for loadbreak operation.